You are here > Products  » EExe Reducers

EExe Reducers from Raxton


Raxton EExe Reducers
effectively reduce the threaded entry diameter of an enclosure to accept a gland or fitting with a smaller thread.

Reducers may also be supplied to accept smaller glands of alternative threads.

Following the basic rules in line with good engineering practices no more than one Reducer should be used at any one time. Stopping Plugs should be fitted directly into unused entries of the equipment and not into a Reducer.

Brass Reducers are supplied with a hexagonal head as standard where space is a critical factor Adaptors with a circular head can be offered with a diameter equal to the across flats dimension of the hexagonal head.

EExe reducers Type BJNylon Reducers are designed with a circular head.

EExe Reducers are supplied with an ‘O’ ring to maintain the IP integrity of the installation.

Raxton EExe Reducers are marked with the applicable approval number and size.

Independently tested to IP68.

EExe reducers nylonImages shown: Type BB Hex (top) and Type BJ Round.


Quality
SIRA (0518) 02 ATEX M207
BVQI EN ISO 9001: 2000

Thread specification
Isometric (ISO) to BS3643:1981 and ISO 965 Pts 1 & 3
EExe reducers Type BJImperial (ET) to BS31:1940 (1979)
National Pipe Thread (NPT) to ANSI/ASME:1983
British Standard Pipe (BSP) to BS21:1985
Pg to DIN 40430:1971

Materials
Brass: BS2874: 1985 CZ121
EExe reducersMild Steel: BS970 PT3 230M07
Stainless Steel: BS970 PT3 316 S11
Aluminium: BS1474/1 6082 T4 or T6
Aluminium Bronze: BS1400 1985 AB2 or BS2874:1986 CA104
Nylon: 30% Glass filled Nylon 66

Approvals
SIRA 00ATEX1073U
IECEx SIR07.0010X
GOST POCC GB.MЛ14.B00104

Plating
Raxton Metallic Reducers are available in a variety of finishes including Nickel, Electro Zinc, Zinc Passivated, Chromatised, Electroless Nickel and Anodised.

Thread identification
A Selection Table is available as a downloadable PDF document (82 KB) and identifies the standard thread variations produced and is designed to assist the user in the selection process. Click here to download.

Part numbering system
The Raxton part numbering system document is available as a 100 KB PDF document.
Click here to download.

Temperature
The item is classified as a component and is therefore not given a temperature rating.
'O' ring -50°c to 100°c
Nylon -20°c to 60°c.